Regulation options

Basic, the LMU controller on the boiler makes it possible to manage a pump-controlled heating network (an optional QAC 34 external probe allowing to slide the temperature on the boiler, and allow for daily and weekly programming), as well as a sanitary hot water network with a spherical exchanger (ECS QAZ 36 probe optional).

RVS 63 Kit (with additional mandatory interface: one OCI 420 per boiler)


This kit includes a RVS 63 regulator, a digital built-in interface in the front of the boiler, three QAD 36 probes,
an external QAC 34 probe and wiredrawing mill of integration and the wiring integration.

• Cascade management for up to 15 boilers

• Management of a DHW pump network

• Management of two networks controlled by V3V, weekly programming

• Management of a direct network (on pump)

• 2 0-10 V inputs and 4 probe inputs

• 4 outputs, a 0-10 V output for controlling variable speed pumps

Maximum of 1 RVS per boiler

RVS 46 Kit (with additional mandatory interface: OCI 420)


This kit includes a RVS 46 regulator, a digital built-in interface in the front of the boiler, a QAD 36 network probe,
an external QAC 34 probe and the wiring integration.

• Management of one network controlled by V3V, weekly programming
Maximum of 1 RVS per boiler

Plug-in for RVS 46: AVS75

This kit is made up of the module, a QAD 36 network probe and wiring integration.

• Management of a VCV controlled network.
ATTENTION: Only 1 AVS 75 can be added to 1 boiler provided with a RVS 46

AGU 2.500

This interface makes it possible to add the management of a V3V controlled (3 point) network or pump with weekly programming.

• The kit includes the AGU 2.500 interface, a QAD 36 network departure probe, an external QAC 34 probe and the wiring integration in the boiler’s control panel.
CAUTION: this interface is not usable within the framework of a cascade.
A single AGU 2.500 can be connected to the boiler, the front-placing of it remains free to place 1 RVS 63 regulator or 1 RVS 46 regulator.
Click on the picture to read it
Click on the picture to read it

ACCESSORIES TO BE CONNECTED TO THE BOILER

QAD 36 Applied probe on heating network

QAC 34 External probe for the boiler that allows for regulation of the temperature coming out of the boiler

QAZ 36 Probe with DHW cable

OCI 420 Communication interface making it possible to receive information coming from external regulators communicating by LPB bus, also consider where using a RVS 46 or RVS63 type regulator

AGU 2.511 0-10 V interface making it possible to receive instructions coming from external regulators communicating in 0-10 V

AGU 2.513 1-20mA which makes it possible to receive instructions coming from external regulators communicating in 4-20mA

AGU 2.515 Interface with two programmable relay exits

QAA 73 Ambient thermoresistor and remote control for boiler: it can only be used with external QAC 34 probe

QAA 75 Ambient thermoresistor and remote control for RVS regulator: it can only be used on its own

Radio Kit Radio connection kit for external probe (1 antenna next to the boiler and a RF transmitter, next to the external probe) Requires an RVS regulator

RVS 63 Kit

RVS 46 Kit

AGU 2.500